Autotransformer


Introduction

Previously we already discussed basics of single phase transformer and three phase transformer. We also discussed about three phase transformer connections or Vector Groups. Now, here we will discuss about auto-transformers. Auto transformers have several applications. But first we will develop some basic concepts of autotransformer. Before proceeding further one should have some basic knowledge of transformer.

Auto transformers can be made in two ways. In one way it can be realized by additively connecting the primary and secondary windings of the two winding transformer. In other way the autotransformers can be thought of built as a single unit with one continuous winding. We will start from first approach and move to second.

Single Phase Autotransformer

Let us first consider a normal single phase two winding transformer. The schematic diagram of a  transformer is shown in Fig-A(i). We will obtain an autotransformer from this usual transformer.

Let the primary side and secondary side voltage ratings are respectively V1, I and V2, I respectively. Number of turns in primary and secondary side are N1 and Nrespectively. Now let us connect the transformers as shown in Fig-A(ii) with additive polarity. For the analysis purpose for better visibility we rearrange the windings in Fig-A(ii) as shown in Fig-B. Of course here we have shown a load connected across secondary



For the purpose of simplifying the analysis the transformer is considered as ideal. (In case of power transformer the ideal transformer analysis gives quite accurate result). The autotransformer analysis can be very simple if you recall two important concepts of a transformer.

  • The voltage developed in the windings are dependent on the flux linkages. The windings are wound on the same magnetic core so they link the same flux. Hence
                                                            V/ N1= V/ N2

             So whenever voltage V1 exist across primary winding, then voltage V2 will be induced across the
          secondary winding irrespective of changes in connections.
                                   
  •  Similarly the magnetic circuit demands that mmf should be balanced. It implies the primary side ampere turn should equal the secondary side ampere turn. Hence
                                                            I. N1= I. N2

It means current  I2 that flows  in secondary winding is associated with current  Iin primary winding according to above mmf balance formula.



In Fig-B the primary  of autotransformer is taken across both the windings where as secondary is across N2 winding.
The autotransformer is so loaded that the secondary current is I1+I2 . It makes the current flowing in the windings as I1 and I2   which are the rated values.
using KCL and KVL if the primary side voltage and current of the auto transformer is Vp and Ip and secondary side voltage and current of the auto transformer is Vs and Is then,

                                                            V= V1+V
                                                             Ip = I
                                                            Vs = V
                                                             Is = I1+I2.

Now the capacity of the autotransformer is (V1+V2).I1 or (I1+I2).V2

Using the voltage ratio and mmf balance formula it is quite easy to show that the autotransformer capacity formula can be simplified as

                  The capacity of autotransformer = Sa = (V+ V2).I= (I+ I2).V2 = V1 I1 (1 + N/ N1)
                                                                                          = V2 I2 (1 + N/ N1)   

                       Where as the capacity of our original transformer = S =V1 I1 = V2 I2

                                                                          So,   Sa = S(1 + N/ N1)

But (1 + N2 /N1) is always greater than 1.
Hence by forming an autotransformer the capacity of the resulting autotransformer is always more than the original isolated winding type transformer. In the so formed autotransformer it should be remembered that the voltage and current through the windings remains as before i.e the rated values. From the above formula it is clear that larger value of N2/N1  gives larger capacity of the autotransformer. 

In this case the voltage ratio of autotransformer =  (V1+V2)/ V2= V1 / V +1 = (N1 / N) + 1

                                                                Hence   V/ Vs =  (N1 / N) +1 =   (N1 / N) +1

From this formula it is clear that if  N2 /N1 is made large to increase the capacity then the voltage ratio between primary and secondary of autotransformer approaches 1. For this reason auto transformers are advantageous for use in power network when the voltage ratio between both sides is near unity. It is used in grid substations as interconnecting transformers (ICT). The autotransformers are used to interconnect two  different voltage levels. For example interconnection of 400kV and 220kV, 735kV and 345kV and 765kV and 400kV etc.. The voltage ratio should be less than 3:1 for more advantageous use.

Again look at the formula,
                                                     I. N1= I. N2

As we said  N2 /N1 should be large for adavantageous use.

                                      To achieve it, N2  should be much greater than N1

                                      It implies that  I2   will be much less than I1

The current I2  flows in the common winding of the autotransformer. Hence the auto transformer can be designed with N2 number of turns made of conductor of smaller cross section area, so resulting in a big saving.The autotransformers are cheaper and lighter in comparison to two winding transformers.

Just looking at the sketch you may think that instead of connecting two windings in additive ways. Why should not it be made of single winding and one terminal brought out from the middle as per requirement. Yes this is true and the autotransformer can be thought of made of a single winding having a part of winding common to primary and secondary .

Sometimes this method is used to obtain a variable secondary voltage. This case it is so designed that the middle contact can smoothly slides over the coil. It is commonly used in the academic electrical laboratories. This is usually called as Variac(Fig-C) or Dimmerstat. There are some other terminologies adopted by different manufacturers.  In this design it is not possible to adopt conductors of two different cross sectional area as in case of ICT where turns ratio is fixed(due to fixed voltage ratio) between primary and secondary. 

Autotransformers are also used for voltage regulation in distribution networks, for starting of induction motors and as lighting dimmers. Autotransformers are also used in electric traction.



One main disadvantage about autotransformer is that the primary and secondary are electrically connected.  So the electrical disturbance i.e high voltage transients from one side can be easily transmitted to the other side.
The other disadvantage is that the impedance of the autotransformer is considerably low, so the short circuit current will be more. More over an open circuit in common winding results in full primary side voltage across the load which is harmful.

But in several cases the advantages outweigh the disadvantages.

Three Phase Autotransformer

First thing is that the theory of single phase autotransformer is the basis of three phase autotransformer. Three single phase autotransfor bank can be used for forming a three phase transformer or a single unit  three phase autotransformer can be built. The three phase autotransformers (see Fig-D) are connected in star-star(Wye-Wye). If the autotransformers are connected as Delta-Delta, then phase difference between primary and secondary exist which is not desired (See Vector Groups).  


In three phase Y-Y connected power autotransformers an additional delta connected winding is used to take care of zero sequence currents (for unbalanced systems), and third harmonic currents.

Although we discussed here is for one particular case still we revealed the general approach. If you wish to connect load across the other winding, then you can proceed in a similar way.

Moreover the above analysis is for step down case. You can easily analyze for step up case by interchanging the position of source and load. In this case the direction of I1+I2 is reversed so also the directions of Iand I2. It should be recalled again that the change of direction of current in series winding is associated with change of direction of current in common winding to satisfy  mmf balance.






10 comments:

Vandana Transformers said...

Vandana Transformers in Bangalore
http://www.vandanatransformers.com/Home.html

synthesis said...

Synthesis Winding Technologies Pvt. Ltd as a leading manufacturer and exporter of automatic winding machines. For nearly two decades, we are involved in design, manufacture and sales of a comprehensive range of Winding machines, CCoil Winding Machines, Winding machines, Automatic Winding Machines, Transformer Winding Machines, aero space, defence in bangalore, India
http://www.synthesisindia.com

synthesis said...

Synthesis India - Coil Winding Machines, Automatic Winding Machines comprises of various Automatic Winding Machines that are specifically designed to cater to the winding needs of various Sectors like auto component, Electrical and Electronics, white goods, etc.

Anonymous said...

Great article. Thanks.

Senthur Pandian said...

Hi very nice blog regarding Auto Transformers. Found it very useful. Thanks for posting.

Ronald said...

helped me to develop a good understanding

Anonymous said...

Nice work.

Balasti Ganesh said...

i got here veri detailed information on Auto Transformer Principle of Operation,Working

Anonymous said...

Nice explaination thank you.. and why cant u add a numerical example(just a suggestion)???

Anonymous said...

what is cooling of auto transformer?

Post a Comment